SoftingSofting

Ethernet Addressable ControllersSiemens SIMATIC S5/S7 and Siemens-compatible controllers (e.g. VIPA), Modbus TCP controllers (Wago, Beckhoff, Phoenix Contact, Schneider Electric, etc.), Rockwell SLC-500, PLC-5, ControlLogix and CompactLogix, Mitsubishi (Melsec-Q), etc.
Ethernet ProtocolsTCP/IP, RFC1006 (ISO on TCP), ISO (H1), S5, S7, TCP/IP with PLC header, Rockwell SLC-500, PLC-5 and CLX, Modbus TCP, Melsec-Q, raw data
Ethernet Interfaces2 x independent interfaces TP (RJ45), 10/100 MBit/s
Embedded OPC UA ServerSymbolic Mapping; Browsing, Read, Write, Subscribe; Self-Discovery Service; possible reconfiguration without device restart; possible multiple Client connections, optional read-only PLC connection; OPC UA Security with password or certificates
Embedded MQTT PublisherEstablishment of MQTT Broker connection, optional user authentication and data encryption, easy topic generation from existing symbols, maximum of 1,000 topics, adjustable publishing interval
Supported DatabasesMySQL, Oracle, DB2, MS-SQL
Other ProtocolsTelnet, SMTP (email notification), OPCpipe (OPC Tunnel)
Supported Engineering Tools for Symbol ImportSIMATIC STEP 7, TIA Portal V13/V14/V15 including Service Packs
LimitationMaximum of 5 PLC connections, 10,000 items in total
Data mapping PLC - database must be structured in 400 tables and 200 items per table
Configuration SoftwareSofting NetCon for device configuration, dataFEED Exporter for symbol import
Power Supply24 VDC, ca. 0,3 A
Ambient ConditionsOperating temperature: 0 °C ... 55 °C, storage temperature: -20 °C ... 70 °C
Dimensions (HxWxL)131mm x 47mm x 111mm
Weightca. 0,4 kg
Mounting35 mm DIN Rail
Protection ClassIP20
CertificationsCE
Open Source License Declarationhttp://opensource.softing.com/IA/Echo/V7/

The bottom line is the Mentor Graphics runtime solutions, integrated with the Softing Industrial Automation’s industrial solutions, streamline the development of device integration and enable. The Softing OPC Easy Connect Suite is a 32-bit application that can be used on 64-bit systems in 32-bit mode without restrictions or performance reduction. Background information from the German.

Softing canSofting

Softing Industrial Automation Gmbh

Industrial

Download Softing Industrial Automation Driver Download

As an industrial multiprotocol gateway, echocollect e offers a modern solution for further processing of process data. The addition 'e' in the product name stands for Ethernet, since the gateway only. Industrial Automation & Control. Find downloads including firmware, release notes, associated software, drivers, tools and utilities. Knowledgebase Support Center. TManager® Enterprise Appliance Transaction Modules (eATM®) enable bi-directional data exchange between enterprise systems and ControlLogix and other controllers and are a hardware alternative to.